  • 原产地上海-上海市
  • 产品摘要

    AMC16-DETT 基站直流电能计量模块主要是针对有共享需求,且开关电源无分用户电量计量功能的基站而设计的。仪表可对六个回路的直流电能进行计量,并可为配套的霍尔传感器提供工作电流,同时可通过上位机软件实现零漂校准,具有遥测、遥 信、遥调、实时电量计量、供电质量异常告警、信息存储及处理、信息交互等功能。


服务

  • 品质保障·资金安全·售后无忧

产品完善度:

更新时间:2026/10/13 14:41:53关注度:494

关键词标签:直流计量表,基站直流电能计量模块,Base,station,dedicated,DC,energy,meter

支付方式:

  • 支付宝 微信 银行转账

Base station dedicated DC energy meter AMC16(L)-DETT is specially designed for base stations where have sharing requirements, and switch power supply is without the function of sub-user metering. The meter could measure 6 circuits DC energy, and supply working current to the matched hall sensors. Meanwhile, it can realize zero drift calibration by upper computer software. have the functions of telemetering,teleindication,teleadjusting, metering at real time, energy quality abnormal alarm, data storage and processing, data interaction. This meter can measure DC power consumption of three operators, providing detail datas for base station.

Project: American Tower Project and Kenya Telecom Tower Power Monitoring Project.


Technical parameterIndex
inputDC rated voltage1 channel: -48VDC
DC current6 channels hall sensors: total 200A/5V, China Telecom, China Mobile, China Unicom and the 1st channel reserve 50A/5V, 2nd
channel reserve 100A/5V.
Commercial power monitoring1 channel: 0-5VDC
Overload capacityVoltage:1.2times continued,2 times continued 1s;
Current: 1.2 times continued,10 times continued 1s.
Accuracy (superposition hall sensors)1%In≤I≤10%In error±2.5%; I>10%In error±2%
Measurement resolutionVoltage output accuracy 0.01V; current output accuracy 0.01A;
power output accuracy 0.01kw; energy output accuracy 0.01kwh
functionsBasic functionMonitor device system time, total voltage, output total current, power, energy, each channel voltage, current, power, energy; LED
indicator display;485 communication
Metering functionStart current: under rated voltage, when the load current value of the meter doesn’t exceed 1% of the max. current, the meter starts.
Shunt running current: when there is no current in the current circuit of the meter, and 85%-125%of the rated voltage is applied on the voltage circuit, the calculator hall not have more than one digital change
Alarm functionDC voltage output low alarm, DC voltage output high alarm, one power down alarm, module voltage loss alarm, metering branch error alarm, internal program error alarm, clock error alarm, memory failure alarm, AC input power failure alarm
Timing functionsupport broadcast timing, could remote timing to the meter through RS485 communication.
CommunicationSingle channel RS485, baudrate 9600bps, can be set to 1200BPS, 2400bps, 4800bps.Communication protocol: standard or custmized
Hall sensor powerPower supply output:+12V/100Ma, -12V/50mA
supply
Clock accuracy≤0.5S/d(23℃), ≤1S/d(-20℃-60℃),
Auxiliary power supplyVoltage range-40V~-60VDC
Power consumptionWhole device≤2W( no hall power supply output)
StorageIt has the storage function of historical power data and historical
alarm information and the memory is 2MB
Insulation resistance≥40MΩ
environmentTemperatureWorking: -20℃~+60℃; storage:-40℃~+70℃
Humidity≤98% no condensation, no corrosive gas place
Altitude≤4000m
Protection levelIP20
Material flame retardentTerminal glow wire temperature 960℃±10℃, shell glow wire temperature 6500℃±15℃
installationStandard 35mm din rail
Lightning protectionVoltage inputPeak value 5kA
(deferential mode)
Auxiliary power supplyPeak value 5kA
(deferential mode)